Our social:

Senin, 06 Februari 2017

20-200 Amp split-core AC current Sensor CTV-D

 

 

 

 

 

 

 

Description

Overview

A split-core AC current sensor responsive over the range of 20 to 200 amps AC for use with U12, UX120, and ZW data loggers with external input channels. With an input current of AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag.

Feature

Features

  • UL listed
  • Sensor power induced from line voltage
  • Self-gripping split-core design for fast installation

Spesification

The country of origin for this product is the United States. To see the full specifications for this product, please see our product manual found under the documentation tab if available.
Range: 20-200 Amps
Accuracy with H8: ±5.0% of full scale
Accuracy with U12: ±4.5% of full scale
Accuracy with UX120-006M: ±2.1% of full scale
Response time (from 10% to 90% of amplitude): see table
Input current: AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag
Voltage rating: 600 VAC
Construction and operating environment: Molded plastic housing for indoor use per UL508; pivoting leg (leg on CTV-D and CTV-E units is fully removable); UL listed.
Cable length: 1.8m cable (6 foot)
Dimensions: see table

Part No.Range (Amps AC)Approximate Response Time (milliseconds)Dimensions
WindowOuter LengthOuter WidthHeight
CTV-A 2–20 440 2.8 cm x 2.3 cm 1.1 in. x 0.9 in. 7.4 cm 2.9 in 6.6 cm 2.6 in 2.5 cm 1.0 in
CTV-B 5–50 200 2.8 cm x 2.3 cm 1.1 in. x 0.9 in 7.4 cm 2.9 in 6.6 cm 2.6 in 2.5 cm 1.0 in
CTV-C 10–100 100 2.8 cm x 2.3 cm 1.1 in. x 0.9 in 7.4 cm 2.9 in 6.6 cm 2.6 in 2.5 cm 1.0 in
CTV-D 20–200 450 3.8 cm x 3.3 cm 1.5 in. x 1.3 in 9.9 cm 3.9 in 11.9 cm 4.7 in 2.8 cm 1.1 in
CTV-E 60–600 490 7.4 cm x 6.4 cm 2.9 in. x 2.5 in 13.5 cm 5.3 in 15.0 cm 5.9 in 2.8 cm 1.1 in