50 Amp Accu-CT Split-Core Current Transformer 333mV Sensor T-ACT-0750-050


 

 

 

 


Description

Overview

The Accu-CT split-core current transformer offers outstanding accuracy and one-handed operation.

Features

  • Unprecedented Linearity
  • Window Opening 0.75 Inch
  • The Accu-CT revenue grade, split-core current transformer offers outstanding linearity and phase angle accuracy with a unique one-handed opening and closing mechanism.
  • Safe: burden resistor built-in, 333 mVac voltage output at rated full scale current, no shorting blocks needed
  • IEEE C57.13 and IEC 60044-1 accuracy: over full temperature range and down to 1% of rated current
  • Exceptionally low phase angle error: essential for accurate power and energy measurements
  • Glove-friendly: easy to open and install with one hand while wearing safety gloves
  • Approvals: UL recognized, CE mark, RoHS

Spesification

To see the full specifications for this product, please see our product manual found under the documentation tab if available.
Accuracy: ±0.75% from 1% to 120% of rated primary current
Phase angle: ±0.5 degrees (30 minutes) from 1% to 120% of rated current
Accuracy standards: IEEE C57.13 class 1.2 and IEC 60044-1 class 1.0
Primary rating: 5 to 250 Amps, 600 Vac, 60 Hz nominal
Output: 333.33 mVac at rated current
Operating temperature: -30°C to 55°C
Safe: integral burden resistor, no shorting block needed, unlessotherwise noted
Standard lead length: 8 ft (2.4 m), 18 AWG
UL recognized, CE mark, RoHS
Assembled in USA: qualified under Buy American provision in ARRA of 2009
Width: 2.38 inches
Height: 2.40 inches
Thickness: 0.90 inches
Window: 0.78 inches