Description

Overview

A split-core AC current sensor responsive over the range of 5 to 50 amps AC for use with U12, UX120, and ZW data loggers with external input channels. With an input current of AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag.
The molded-plastic housing is rated for indoor use per UL508.

Feature

Features

  • UL listed
  • Sensor power induced from line voltage
  • Self-gripping split-core design for fast installation

Spesification

The country of origin for this product is the United States. To see the full specifications for this product, please see our product manual found under the documentation tab if available.
Range: 5-50 Amps
Accuracy with H8: ±5.0% of full scale
Accuracy with U12: ±4.5% of full scale
Accuracy with UX120-006M: ±2.1% of full scale
Response time (from 10% to 90% of amplitude): see table
Input current: AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag
Voltage rating: 600 VAC
Construction and operating environment: Molded plastic housing for indoor use per UL508; pivoting leg (leg on CTV-D and CTV-E units is fully removable); UL listed.
Cable length: 1.8m cable (6 foot)
Dimensions: see table
Part No.Range (Amps AC)Approximate Response Time (milliseconds)Dimensions
WindowOuter LengthOuter WidthHeight
CTV-A 2–20 440 2.8 cm x 2.3 cm 1.1 in. x 0.9 in. 7.4 cm 2.9 in 6.6 cm 2.6 in 2.5 cm 1.0 in
CTV-B 5–50 200 2.8 cm x 2.3 cm 1.1 in. x 0.9 in 7.4 cm 2.9 in 6.6 cm 2.6 in 2.5 cm 1.0 in
CTV-C 10–100 100 2.8 cm x 2.3 cm 1.1 in. x 0.9 in 7.4 cm 2.9 in 6.6 cm 2.6 in 2.5 cm 1.0 in
CTV-D 20–200 450 3.8 cm x 3.3 cm 1.5 in. x 1.3 in 9.9 cm 3.9 in 11.9 cm 4.7 in 2.8 cm 1.1 in
CTV-E 60–600 490 7.4 cm x 6.4 cm 2.9 in. x 2.5 in 13.5 cm 5.3 in 15.0 cm 5.9 in 2.8 cm 1.1 in