Differential Air Pressure Transducer Sensor
Description
The T-VER-PXU-L is a differential
air pressure transducer that utilizes a highly accurate and stable
sensor, which is microprocessor profiled for improved accuracy and
reliability. The stability, accuracy, and ease-of-use characteristics of
the PX models make them the ideal product for differential pressure
monitoring applications.
Requires analog input option
during RX3000 or U30 system configuration and use of a S-FS-CVIA when
using the H22-001 data logger. When using a U12 data logger, this sensor
requires an 0-5 Vdc analog input cable (CABLE-ADAP5) and external power
provided by an AC adapter (AC-SENS-1).
Feature
- User selectable units, uni- or bi-directional pressure ranges and analog output (mA or Vdc)
- LCD display
- Panel or duct mounting (probe included)
- High accuracy
Spesification
To see the full specifications for this product, please see our product manual found under the documentation tab if available.
| Measurement ranges: selectable uni- or bidirectional 0.1, 0.25, 0.5, 1.0, 2.5,5,10 "W.C.; (selectable also in Pascal units) |
| Accuracy: +/- 1% full scale of selected range |
| Sensor supply: 12 - 30VDC or 24 VAC., 35 mA |
| Medium: dry air, inert gas |
| Operating temperature range: 0 to 600C (32 to 1400F) |
| Humidity range: 10 - 90% non-condensing |
| Response time: (selectable) Fast, 2 sec; Standard, 20 sec |
| Output: (selectable) 4 - 20mA or 0 -5VDC or 0 - 10VDC |
| Dimensions: 4.5x3.3x2.2 in (114x84x55 mm) - probe length 8.75 in. (22.23 cm) |
| Weight: 7.2 oz |
| Display (L model only): signed 31/2 digit LCD |
| Case: UL 94 V-O fire retardent ABS |
| Proof pressure: 3 psid (20.6kPa) |
| Burst pressure: 5 psid (34.5kPa) |
| CE |

0 komentar:
Posting Komentar