Description

HOBO 4-Channel Pulse Data Logger is a highly versatile, 4-channel energy data logger that combines the functionality of four separate data loggers into one compact unit. It enables energy management professionals – from energy auditors to building commissioners – to easily track building energy consumption, equipment runtimes, and water and gas flow rates. The HOBO UX120 Pulse Data Logger is available in a standard memory model (UX120-017) capable of 500,000 measurements and anexpanded memory version (UX120-017M) capable of over 4,000,000 measurements

Feature

  • Simultaneously measures and records pulse signals, events, state changes, and runtimes
  • Stores up to over 4 million measurements, enabling longer deployments with fewer site visits
  • Maximum pulse rate – 120 Hz
  • Pulse input range – 0 to 24VDC
  • Streamlines deployment via a range of start/stop options, logger status LEDs, and high-speed USB 2.0 data offload
  • Works with Onset's Energy & Power Meter to measure Power Factor (PF), Reactive Power (VAR), Watt Hours (Wh) and more. Learn how.
    The T-VER-E50B2 Energy and Power Meter outputs (3) sets of pulses which are logged by the UX120-017. These pulses represent Watt-hours, Amp-hours, and VAR-hours. HOBOware software uses these pulse values to calulate AC Current, AC Voltage, kW, Power Factor, VARs, and VA. The formulas used in these calculations can be found here: 14993-A-Derived-Channels.zip
  • Compatible with HOBOware and HOBOware Pro software for logger setup, graphing and analysis


Spesification

The country of origin for this product is the United States. To see the full specifications for this product, please see our product manual found under the documentation tab if available.
Inputs
External Contact Input: Electronic solid state switch closure or logic driven digital signals to 24 V
Maximum Pulse Frequency: 120 Hz
Maximum State, Event, Runtime Frequency: 1 Hz
Bits: 4–32 bits depending on pulse rate and logging interval
Maximum Pulses Per Interval: 7,863,960 (using maximum logging rate)
Driven Logic Signal: Input Low: ≤ 0.4 V; Input High: 3 to 24 V
Absolute Maximum Rating: Maximum Voltage: 25 V DC
Minimum Voltage: -0.3 V DC
Solid State Switch Closure: Input Low: < 10 KΩ; Input High: > 500 KΩ
Internal Weak Pull-Up: 100 KΩ
Input Impedance: Solid state switch closure: 100 KΩ pull up; Driven signal: 4.5 KΩ
Minimum Pulse Width: Contact closure duration: 500 uS; Driven logic signal: 100 uS
Lockout Time: 0 to 1 second in 100 ms steps
Edge Detection: Falling edge, Schmitt Trigger buffer
Preferred Switch State: Normally open or Logic "1" state
Logging
Resolution: Pulse: 1 pulse, Runtime: 1 second, State and Event: 1 State or Event
Logging Rate: 1 second to 18 hours, 12 minutes, 15 seconds
Time Accuracy: ± 1 minute per month at 25°C (77°F) (see Plot A on next page)
Battery Type: Two AA alkaline or lithium batteries
Battery Life: 1 year, typical with logging intervals greater than 1 minute and normally open contacts
Memory
Memory: UX120-017: 520,192 measurements (assumes 8-bit)
UX120-017M: 4,124,672 measurements (assumes 8-bit)
Download Type: USB 2.0 interface
Download Time: 30 seconds for UX120-017, 1.5 minutes for UX120-017M
Physical
Operating Range: Logging: -40° to 70°C (-40° to 158°F); 0 to 95% RH (non-condensing)
Launch/Readout: 0° to 50°C (32° to 122°F) per USB specification
Weight: 149 g (5.26 oz)
Size: 11.4 x 6.3 x 3.3 cm (4.5 x 2.5 x 1.3 inches)
Environmental Rating: IP50